Home » Product List » digital panel meter » Sfdbe Series Multifunctional Network Power Instrument
Product Details
Sfdbe Series Multifunctional Network Power Instrument
| Model NO.: | SFDBE-96T7 |
|---|---|
| Trademark: | SFIM |
| Origin: | CHINA |
This series meter has all the functions of SFDB series digital programmablemeters. It can measure almost more than 30 electrical parameters including of three-phase voltage, three-phase current, active power, reactive power, apparent power, frequency, power factor and 4-quadrant energy etc; It displays through 3-row 4-digit or 2-row 6-digit LED nixietubes or LCD screen. It is added with keyboard parameters such as alarm and transmitting output object, alarm delay time, display object and cycle display time and 2-channel electric energy pulse outputs, 4-channel switching value input and 4-quadrant energy measuring functions. The alarm(or switching value)output and transmitting output can enlarge to four channels.
Basic Parameters:
Input Parameters:
Rated voltage: AC 57.7V, 100V, 220V, 380V
Rated current: AC 1A, 5AFrequency range: 45~65Hz
Input network: 3-phase3-wire, 3-phase4-wire
Accuracy of measurement:
Voltage, current, active power. Reactive power, apparent power: ± 0.5%
Frequency: ± 0.1Hz Power factor: ± 0.01PF
Active electric energy: ± 0.5% reactive electric energy: ± 2.0%
Start: On the condition of rated voltage, reference frequency and COSΦ =1.0,
When load operational current is 0.001In, it can start and measure
The electrical quantity continuously.
Creep: When exerting 115%rated voltage and no current in the current
Circuitry, the instrument is with no electrical quantity accumulation
And pulse output.
Output parameters:
Pulse output: Open-collector optical coupling output, open-collector voltage
VCC≤ 48V, current Lz≤ 500mA
Pulse constant: 10000imp/kWh or 10000imp/kvarh. The meaning is: The
Pulse output 10000imp when the meter accumulate to
1kWh, it stresses that, 1kWh is quadratic electric quantity
Data of elecric quantity. Under the cndition of PT and CT,
The N pulse data responding the primary electric
Energy=1kWh× PT ratio× CT ratio
Alarm(or switching value)output: 4-channel relay normally open contact
Output, 30VDC/1A, 240VAC/1A(resistive load)
Switching value input: 4-channel dry contact(built-in+5V source)
Analog quantity transmitting output: Can provide4-channel outputs at the same time
Output range: DC 0~20mA/4~20mA programmable
Accuracy: ± 0.5%
Overload: 120% actual output, Max current is 24mA
Load: ≤ 400Ω
Communication interface: RS485 serial
Communication, applying MODBUS_RTU communication protocol